UPS

Online UPS 1kVA~30kVA EA800 Series
True on-line dual conversion design.
Sine wave pulse width modulation.(SPWM) .
IGBT inverter design.
Wide Input voltage window.
True sine wave output with less than 3% THD.
Extendable backup time.
Generator compatible.
Cold start.
EMI/RFI filter.
Load/battery capacity display.
Overload, on-line, battery status LED/LCD display.
Advanced Battery Management.
Zero transfer time .
RS-232 .
Optional SNMP card.

Specifications

Model

EA801

EA802

EA803

EA804

EA806

EA808

EA810

EA815

EA820

EA830

Capacity

1KVA

2KVA

3KVA

4KVA

6KVA

8KVA

10KVA

15KVA

20KVA

30KVA

Input

Voltage Range

220VAC+/-25% 380VAC+/-20%

Frequency

50/60Hz+/-5%

Phase

Single Phase +N / Three Phases +N

Output

Waveform

True Sine Wave

Voltage Range

220VAC+/-1%

Frequency

50/60Hz +/- 0.5%

THD

<3%(Linear Load)

Power Factor

Current Limitation, Shutdown Automatically

Short Circuit Protection

0.8

Overload Capability

Overload(110%~150%), Transfer to Bypass after 20s, Automatically Recover when the Load Comes back to Normal.

Battery

Type

Sealed Lead-Acid, Maintenance-Free

DC

48VDC

192VDC

Charge Voltage

55V

220V

Charge Time

90% Capacity after 8 Hours

System

Control Technology

SPWM

Overload

125% for 1Min  150% for 1s

Output PF

0.8

Transfer Time

0ms

Efficiency

>85%

Display

LCD

Operating Mode, I/P and O/P Voltage, I/P and O/P Frequency, Battery Voltage, Load Percentage, UPS
Internal Temperature

LED

Low Battery, Online, Inverter, Bypass, Abnormal

Communication

RS232

Monitoring Function

1.Power 2.UPS Shutdown 3.Monitor UPS Status 4.UPS Self-test 5.Auto-save Files

Protection

Short circuit,  Over-temp, Battery Low, Output Low, Surge

Audible Noise

<60db( 1 Meter)

Environment

Temperature

0~40 C

Humidity

0%~95%

Net Weight(No Battery)Kg

35

57

68

62

66

100

110

200

245

300

Dimension(WxDxH)mm

210x490x500

210x580x540

230x540x570

305x585x870

380x700x980

430x810x1100

EA800